Flame Retardant and Halogen-Free Cable

1 ОГНЕСТОЙКИЙ и БЕЗГАЛОГЕНОВЫЙ КАБЕЛЬ (2)

Fireproof

NHXH-FE 180/E30
(HXH-FE 180/E30)

Cable with copper conductors, silicone rubber insulation, filler, sheath made of halogen-free polymer compositions

Structure Application Characteristics

The cable consists of: Conductive copper core 1, 2 classes according to GOST 22483, IEC 60228. FLEX – 3-5 classes according to GOST 22483, IEC 60228, silicone rubber insulation, halogen-free filling mm2 inclusive, it is allowed to apply an outer sheath with filling the cavities between the cores with the material of the outer sheath. In this case, the inner filling is not applied, the sheath is made of a polymer composition that does not contain halogens.

Flame-resistant halogen-free cables are intended for power transmission systems in stationary installations, as well as for connection to stationary electrical appliances, devices, and assembly of electrical switchgear for power networks with a rated voltage of up to 0.6/1 kV. The cables provide transmission of electrical energy, control and management signals to electrical equipment, the functioning of which in fire conditions is mandatory for rescue operations. They are used at facilities with increased fire safety requirements for single and bundled cables in rooms, tunnels, trays, pipes, flexible hoses in the absence of danger of mechanical damage and protection from ultraviolet rays.

Rated voltage: 0.6/1 kV

Test voltage: 4 kV/50 Hz

Temperature range: during installation: up to -15 °C during operation: from -30 °C to +50 °C cores: no more than +90 °C short circuit: no more than +250 °C/4 sec in emergency mode: no more than +130 °C/8 h per day

Bending radius (minimum): single-core cables: no less than 10 diameters; multi-core cables: no less than 7.5 diameters for cables with FLEX index: no less than 6 diameters

Number and nominal cross-section of conductors

(mm²)

Rated cable diameter (mm)

Estimated weight of 1 km of cable

(kg) (reference)

Electrical resistance of wires, in accordance with

GOST 22483, IEC 60228,

not more than (Ohm/km)

HXH-FE 180E30, (N)HXH-FE 180E30

1 x 25

10,4

307,5

0,727

1 x 35

11,7

405,1

0,524

1 x 50

13,5

554,7

0,387

1 x 70

15,1

755,1

0,268

1 x 95

17,1

1 024,90

0,193

1 x 120

19,1

1 233,90

0,153

1 x 150

20,4

1 524,20

0,124

1 x 185

23

1 938,60

0,0991

1 x 240

25,8

2 426,10

0,0754

2 x 1,5

8,5

112,8

12,1

2 x 2,5

9,3

145,1

7,41

2 x 4

10,3

191,4

4,61

2 x 6

11,3

247,4

3,08

2 x 10

13

358,1

1,83

2 x 16

16,8

602,4

1,15

3 x 1,5

9

132,8

12,1

3 x 2,5

9,9

174,5

7,41

3 x 4

10,9

234,8

4,61

3 x 6

12,2

314,9

3,08

3 x 10

13,9

454,2

1,83

3 x 16

17,8

753,3

1,15

4 x 1,5

9,8

158,3

12,1

4 x 2,5

10,7

210,5

7,41

4 x 4

12,1

292,6

4,61

4 x 6

13,3

386,8

3,08

4 x 10

15,2

563,8

1,83

4 x 16

19,6

942

1,15

4 x 25

23,8

1 432,70

0,727

4 x 35

26,8

1 888,30

0,524

4 x 50

30,8

2 569,80

0,387

4 x 70

35,2

3 492,80

0,268

4 x 95

40,4

4 745,60

0,193

4 x 120

45,6

5 744,80

0,153

4 x 150

48,5

7 053,60

0,124

4 x 185

54,4

8 938,80

0,0991

4 x 240

61,7

11 301,90

0,0754

5 x 1,5

10,7

186,3

12,1

5 x 2,5

11,7

249,7

7,41

5 x 4

13,2

349,5

4,61

5 x 6

14,6

463,9

3,08

5 x 10

16,7

680,5

1,83

5 x 16

21,5

1 130,00

1,15

5 x 25

26,1

1 724,50

1,727

5 x 35

29,7

2 293,20

0,524

5 x 50

33,9

3 107,20

0,387

5 x 70

38,8

4 228,30

0,268

5 x 95

44,7

5 754,90

0,193

5 x 120

50,7

6 985,60

0,153

NHXH-FE 180/E90
(N)HXH-FE 180/E90)

Cable with copper conductors, silicone rubber insulation, filler, sheath made of halogen-free polymer compositions

Structure Application Characteristics

The cable consists of: Conductive copper core 1, 2 classes according to GOST 22483, IEC 60228. FLEX – 3-5 classes according to GOST 22483, IEC 60228, silicone rubber insulation, halogen-free filling mm2 inclusive, it is allowed to apply an outer sheath with filling the cavities between the cores with the material of the outer sheath. In this case, the inner filling is not applied, the sheath is made of a polymer composition that does not contain halogens.

Flame-resistant halogen-free cables are intended for power transmission systems in stationary installations, as well as for connection to stationary electrical appliances, devices, and assembly of electrical switchgear for power networks with a rated voltage of up to 0.6/1 kV. The cables provide transmission of electrical energy, control and management signals to electrical equipment, the functioning of which in fire conditions is mandatory for rescue operations. They are used at facilities with increased fire safety requirements for single and bundled cables in rooms, tunnels, trays, pipes, flexible hoses in the absence of danger of mechanical damage and protection from ultraviolet rays.

Rated voltage: 0.6/1 kV

Test voltage: 4 kV/50 Hz

Temperature range: during installation: up to -15 °C during operation: from -30 °C to +50 °C cores: no more than +90 °C short circuit: no more than +250 °C/4 sec in emergency mode: no more than +130 °C/8 h per day

Bending radius (minimum): single-core cables: no less than 10 diameters; multi-core cables: no less than 7.5 diameters for cables with FLEX index: no less than 6 diameters

Number and nominal cross-section of cores (mm²)

Rated cable diameter (mm)

Estimated weight of 1 km of cable (kg) (reference)

Electrical resistance of wires, in accordance with GOST 22483, IEC 60228, not more than (Ohm/km)

HXH-FE 180/E90, (N)HXH-FE 180/E90

2 x 1,5

12,9

235

12,1

2 x 2,5

13,7

273

7,41

2 x 4

14,7

355

4,61

2 x 6

15,7

426

3,08

2 x 10

17,2

551

1,83

2 x 16

19,6

750

1,15

2 x 25

22,9

1 070

0,727

2 x 35

25,4

1 364

0,524

2 x 50

28,8

1 804

0,387

2 x 70

32,6

2 395

0,268

2 x 95

37,2

3 201

0,193

2 x 120

40,4

3 802

0,153

2 x 150

44,2

4 666

0,124

2 x 185

49,4

5 871

0,0991

2 x 240

55,8

7 417

0,0754

3 x 1,5

13,5

287

12,1

3 x 2,5

14,4

342

7,41

3 x 4

15,4

417

4,61

3 x 6

16,4

508

3,08

3 x 10

18,1

674

1,83

3 x 16

20,7

935

1,15

3 x 25

24,3

1 354

0,721

3 x 35

27,2

1 761

0,254

3 x 50

30,8

2 343

0,387

3 x 70

34,9

3 129

0,268

3 x 95

39,8

4 202

0,193

3 x 120

43,7

5 051

0,153

3 x 150

47,3

6 151

0,124

3 x 185

52,9

7 757

0,0991

3 x 240

59,7

9 801

0,0754

4 x 1,5

14,4

326

12,1

4 x 2,5

15,3

393

7,41

4 x 4

16,5

486

4,61

4 x 6

17,7

599

3,08

4 x 10

19,6

807

1,83

4 x 16

22,4

1 130

1,15

4 x 25

26,4

1 652

0,727

4 x 35

29,6

2 158

0,524

4 x 50

34,3

2 943

0,387

4 x 70

38,3

3 889

0,268

4 x 95

44,2

5 286

0,193

4 x 120

47,6

6 236

0,153

4 x 150

52,3

7 727

0,124

4 x 185

58,8

9 813

0,0991

4 x 240

66

12 284

0,0754

5 x 1,5

15,4

367

12,1

5 x 2,5

16,5

447

7,41

5 x 4

17,8

558

4,61

5 x 6

19,1

693

3,08

5 x 10

21,2

943

1,83

5 x 16

24,4

1 330

1,15

5 x 25

29,1

1 971

1,727

5 x 35

33,3

2 638

0,524

5 x 50

37,8

3 520

0,387

5 x 70

42,9

4 736

0,268

5 x 95

49

6 370

0,193

5 x 120

53,2

7 582

0,153

JE-H(St)…Bd FE 180/E30

The cable is fire-resistant with copper conductors twisted in pairs, silicone rubber insulation, aluminum screen, and a halogen-free polymer sheath.

Structure Application Characteristics

The cable consists of: a conductive core - copper, single-wire, class A according to GOST 4809:2007; silicone rubber insulation; insulated cores twisted into pairs, pairs - into bundles, over the bundle is wrapped with PET film, an aluminum foil screen, a sheath made of non-flammable, halogen-free polymer composition.

Transmission of electrical signals of information, control and management in industrial electronics, fire and security alarm systems with a rated voltage of up to 300 V. For laying in facilities with increased fire safety requirements, where cable operation in fire conditions is mandatory, for single and bundle laying in rooms, tunnels, in trays, boxes, flexible sleeves in the absence of danger of mechanical damage.

Rated voltage: 0.3 kV

Test voltage: 2 kV

Temperature range: during installation: not lower than -5 ° C during operation: from -30 ° C to +70 ° C heating of cores: not higher than +70 ° C

Bending radius (minimum): not less than 7.5 diameters

Number and nominal cross-section of cores (pcs x mm)

Estimated wire diameter (mm)

Estimated mass of 1 km of cable (kg)

1 х 2 х 0,8

 

 

2 х 2 х 0,8

7,5

65

4 х 2 х 08

9,5

104

6 х 2 х 08

  

8 х 2 х 0,8

11,5

165

10х 2 х 0,8

  

12 х 2 х 0,8

13,5

235

16 х 2 х 0,8

15

300

20 х 2 х 0,8

16,5

361

 

JE-H(St)…Bd FE 180/E90

The cable is fire-resistant with copper conductors twisted in pairs, silicone rubber insulation, aluminum screen, and a halogen-free polymer sheath.

Structure Application Characteristics

The cable consists of: a conductive core - copper, single-wire, class A according to GOST 4809:2007; silicone rubber insulation; insulated cores twisted into pairs, pairs - into bundles, over the bundle is wrapped with PET film, an aluminum foil screen, a sheath made of non-spreading, halogen-free polymer composition.

Transmission of electrical signals of information, control and management in industrial electronics, fire and security alarm systems with a rated voltage of up to 300 V. For laying in facilities with increased fire safety requirements, where cable operation in fire conditions is mandatory, for single and bundle laying in rooms, tunnels, in trays, boxes, flexible sleeves in the absence of danger of mechanical damage.

Rated voltage: 0.3 kV

Test voltage: 2 kV

Temperature range: during installation: not lower than -5 ° C during operation: from -30 ° C to +70 ° C heating of cores: not higher than +70 ° C

Bending radius (minimum): not less than 7.5 diameters

 

Number and nominal cross-section of cores (pcs x mm)

Estimated wire diameter (mm)

Estimated mass of 1 km of cable (kg)

1 х 2 х 0,8

 

 

2 х 2 х 0,8

8,5

83

4 х 2 х 0,8

11,5

138

6 х 2 х 0,8

  

8 х 2 х 0,8

15

243

10 х 2 х 0,8

  

12 х 2 х 0,8

18,5

351

16 х 2 х 0,8

20,5

441

20 х 2 х 0,8

24

557

Halogen-free

J-H(St)H Bd Halogen-free cable for signaling

Structure Application Characteristics

- Bare copper conductor, solid

- Core insulation: HFFR compound

- Core color coding according to

- 4 cores twisted in a quadruple star,

- Tape shielded with tinned copper drain wire (0.80 mm)

- Outer sheath made of HFFR compound

Sheath color red.

Halogen-free cables J-H(St)H...Bd are used for signaling, transmission and telecommunications in fixed indoor wiring. The screen provides protection against external interference. Non-flammable cables are used in schools, airports, hospitals, etc., where in the event of a fire, the release of toxic gases into the environment is unacceptable. In the event of a fire, these cables delay the spread of fire and emit a minimum amount of smoke.

  • Number of cores: from 1 to 10 pairs
    Diameter: from 0.6 to 1.38 mm
    Permissible temperature limits:

  • - stationary - from -30 ° C to +70 ° C

  • - mobile - from -5 ° C to +50 ° C

  • Insulation resistance (loop): 0.60 mm = 130 Ohm/km
    Insulation resistance, min.: 100 MOm/km
    Total capacitance (800 Hz), max.: 100 nF/m
    Capacitive unbalance (k), min.: 300 pF/100m
    Operating voltage, peak: 300 V
    Test voltage (AC 50 Hz): core/core - 800 V
    Minimum cable bending radius: 7.5 x cable Ø

Name

Number of cores / Ø, mm

External Ø, mm

Copper weight kg/km

Cable weight kg/km

J-H(St)H Bd 1x2x0,60 мм

1x2xØ0,60

4,6

8,15

31

J-H(St)H Bd 2x2x0,60 мм

2x2xØ0,60

5,1

13,67

42

J-H(St)H Bd 4x2x0,60 мм

4x2xØ0,60

8

24,71

75

J-H(St)H Bd 6x2x0,60 мм

6x2xØ0,60

8,5

35,75

94

J-H(St)H Bd 10x2x0,60 мм

10x2xØ0,60

10,1

57,83

136

J-H(St)H Bd 1x2x0,80 мм

1x2xØ0,80

5,4

14,61

44

J-H(St)H Bd 2x2x0,80 мм

2x2xØ0,80

6,1

24,61

63

J-H(St)H Bd 4x2x0,80 мм

4x2xØ0,80

10

44,61

114

J-H(St)H Bd 6x2x0,80 мм

6x2xØ0,80

10,6

64,55

147

J-H(St)H Bd 10x2x0,80 мм

10x2xØ0,80

12,5

104,39

228

J-H(St)H Bd 20x2x0,80 мм

20x2xØ0,80

16,6

203,99

404

N2XH (ПвПГнг-HF) halogen-free, flame-retardant cables

Cable with cross-linked polyethylene insulation and a sheath made of halogen-free, flame-retardant polymer compositions with low smoke and gas emission.

Structure Application Characteristics

The cable consists of:

  • conductive core of class 1, 2,
  • insulation of cross-linked polyethylene,
  • filling of halogen-free, non-flammable composition,
  • sheath of polymer composition that does not contain halogens.

Cables are intended for transmission and distribution of electric energy in stationary alternating current installations with a voltage of 0.6/1 kV. Cables are used for laying in production and office premises in which computers and other microprocessor equipment are installed, as well as in subway structures, residential and public buildings, cable structures and premises with increased fire safety requirements. The cable meets fire safety requirements

Cables are intended for transmission and distribution of electric energy in stationary alternating current installations with a voltage of 0.6/1 kV. Cables are used for laying in production and office premises in which computers and other microprocessor equipment are installed, as well as in subway structures, residential and public buildings, cable structures and premises with increased fire safety requirements. The cable meets fire safety requirements

N2XH (ПГнг-HF)

Number and nominal cross-section of conductors

(mm²)

 

 

Rated cable diameter (mm)

Estimated weight of 1 km of cable

(kg) (reference)

Electrical resistance of conductors,

not more than (Ohm/km)

1 x 1,5

5,4

42

12,1

1 x 2,5

5,8

54

7,41

1 x 4

6,6

76

4,61

1 x 6

7,1

98

3,08

1 x 10

7,9

139

1,83

1 x 16

9,3

201

1,15

1 x 25

10,8

296

0,727

1 x 35

11,9

391

0,524

1 x 50

13,8

534

0,387

1 x 70

15,3

731

0,268

1 x 95

17,4

985

0,193

1 x 120

19

1 188

0,153

1 x 150

20,5

1 462

0,124

1 x 185

22,9

1 853

0,0991

1 x 240

25,6

2 320

0,0754

2 x 1,5

9,3

120

12,1

2 x 2,5

10,1

152

7,41

2 x 4

11,9

216

4,61

2 x 6

12,9

272

3,08

2 x 10

14,6

385

1,83

2 x 16

17

552

1,15

2 x 25

20,5

831

0,727

2 x 35

23,2

1 100

0,524

2 x 50

26,4

1 472

0,387

2 x 70

29,8

1 970

0,268

2 x 95

33,8

2 640

0,193

2 x 120

36,8

3 149

0,153

2 x 150

39,8

3 853

0,124

2 x 185

44,6

4 879

0,0991

2 x 240

50,4

6 159

0,0754

3 x 1,5

9,8

137

12,1

3 x 2,5

10,6

179

7,41

3 x 4

12,5

257

4,61

3 x 6

13,8

338

3,08

3 x 10

15,5

478

1,83

3 x 16

18

695

1,15

3 x 25

21,8

1 055

0,727

3 x 35

24,6

1 406

0,524

3 x 50

28,1

1 896

0,387

3 x 70

31,7

2 257

0,268

3 x 95

36

3 451

0,193

3 x 120

39,4

4 142

0,153

3 x 150

42,6

5 098

0,124

3 x 185

47,8

6 463

0,0991

3 x 240

54

8 145

0,0754

4 x 1,5

10,5

161

12,1

4 x 2,5

11,5

213

7,41

4 x 4

13,8

316

4,61

4 x 6

15

411

3,08

4 x 10

16,9

589

1,83

4 x 16

20

874

1,15

4 x 25

24,1

1 331

0,727

4 x 35

27,1

1 764

0,524

4 x 50

31,4

2 416

0,387

4 x 70

35,5

3 266

0,268

4 x 95

40,2

4 414

0,193

4 x 120

43,8

5 276

0,153

4 x 150

47,6

6 530

0,124

4 x 185

53,3

8 278

0,0991

4 x 240

60,7

10 483

0,0754

5 x 1,5

11,4

187

12,1

5 x 2,5

12,5

250

7,41

5 x 4

15

373

4,61

5 x 6

16,4

488

3,08

5 x 10

18,5

705

1,83

5 x 16

21,9

1 051

1,15

5 x 25

26,6

1 605

0,727

5 x 35

30,1

2 148

0,524

5 x 50

34,6

2 927

0,387

5 x 70

39,2

3 966

0,268

5 x 95

44,7

5 391

0,193

5 x 120

48,9

6 470

0,153

NА2XH (АПвПГнг-HF)

Cable with aluminum conductors, with cross-linked polyethylene insulation and a sheath made of halogen-free, flame-retardant polymer compositions with low smoke and gas emission.

Structure Application Characteristics

The cable consists of:

  • conductive core 1, 2 class,
  • crosslinked polyethylene insulation,
  • filling of halogen-free non-combustible composition,
  • sheath of polymer composition that does not contain halogens.

Cables are intended for transmission and distribution of electric energy in stationary alternating current installations with a voltage of 0.6/1 kV. Cables are used for laying in production and office premises in which computers and other microprocessor equipment are installed, as well as in subway structures, residential and public buildings, cable structures and premises with increased fire safety requirements. The cable meets fire safety requirements

The cables are designed for transmission and distribution of electrical energy in stationary alternating current installations with a voltage of 0.66/1 kV. The cables are used for laying in production and office premises in which computers and other microprocessor equipment are installed, as well as in subway structures, residential and public buildings, cable structures and premises with increased fire safety requirements.

Rated voltage: 0.6/1 kV

Test voltage: 3/3.5 kV

Temperature range:

during installation: up to -15 °C;

during operation: from -50 to +50 °C in emergency mode: no more than +130 °C/8 hours per day

Bending radius (minimum): single-core cables: not less than 10 diameters; multi-core cables: not less than 7.5 diameters

NА2XH (АПвПГнг-HF)

Number and nominal cross-section of cores

(mm²)

Rated cable diameter (mm)

Estimated weight of 1 km of cable

(kg) (reference)

Electrical resistance of conductors,

not more than (Ohm/km)

1 х 16

9,3

109

1,91

1 х 25

10,8

153

1,2

1 х 35

11,9

187

0,868

1 х 50

13,8

243

0,641

1 х 70

15,3

318

0,443

1 х 95

17,4

409

0,32

1 х 120

19

505

0,253

1 х 150

20,5

615

0,206

1 х 185

22,9

757

0,164

1 х 240

25,6

953

0,125

2 х 2,5

10,12

138

12,1

2 х 4

11,86

167

7,41

2 х 6

12,86

201

5,11

2 х 10

14,62

262

3,08

2 х 16

16,44

364

1,91

2 х 25

20,5

547

1,2

2 х 35

23,2

666

0,868

2 х 50

26,4

919

0,641

2 х 70

29,8

1 199

0,443

2 х 95

33,8

1 583

0,32

2 х 120

36,8

1 946

0,253

2 х 150

39,8

2 387

0,206

2 х 185

44,6

3 003

0,164

2 х 240

50,4

3 678

0,125

3 х 2,5

10,62

149

12,1

3 х 4

12,49

181

7,41

3 х 6

13,77

220

5,11

3 х 10

15,45

290

3,08

3 х 16

18,01

406

1,91

3 х 25

21,75

611

1,2

3 х 35

24,64

751

0,868

3 х 50

28,08

1 031

0,641

3 х 70

31,72

1 371

0,443

3 х 95

36,01

1 822

0,32

3 х 120

39,43

2 190

0,253

3 х 150

42,64

2 696

0,206

3 х 185

47,77

3 392

0,164

3 х 240

53,99

4 193

0,125

4 х 2,5

11,5

168

12,1

4 х 4

13,79

207

7,41

4 х 6

15

253

5,11

4 х 10

16,88

337

3,08

4 х 16

19,27

494

1,91

4 х 25

24,12

717

1,2

4 х 35

27,14

912

0,868

4 х 50

31,39

1 234

0,641

4 х 70

35,45

1 659

0,443

4 х 95

40,23

2 159

0,32

4 х 120

43,84

2 621

0,253

4 х 150

47,62

3 252

0,206

4 х 185

53,32

4 064

0,164

4 х 240

60,67

5 054

0,125

5 х 2,5

12,47

190

12,1

5 х 4

15,02

235

7,41

5 х 6

16,37

290

5,11

5 х 10

18,48

388

3,08

5 х 16

21,13

571

1,91

5 х 25

26,55

859

1,2

5 х 35

30,12

1 063

0,868

5 х 50

34,64

1 439

0,641

5 х 70

39,16

1 940

0,443

5 х 95

44,69

2 553

0,32

5 х 120

48,94

3 118

0,253

NHXMH ( ППГнг-HF)

Cable with aluminum conductors, with cross-linked polyethylene insulation and a sheath made of halogen-free, flame-retardant polymer compositions with low smoke and gas emission.

Structure Application Characteristics

The cable consists of: a conductive core 1, 2, insulation made of a halogen-free polymer composition, filling of a halogen-free, non-flammable composition, sheath made of a halogen-free polymer composition.

Cables are designed for transmission and distribution of electrical energy in stationary alternating current installations with a voltage of 0.6/1 kV. Cables are used for laying in production and office premises in which computers and other microprocessor equipment are installed, as well as in subway structures, residential and public buildings, cable structures and premises with increased fire safety requirements.

Rated voltage: 0.6/1 kV

Test voltage: 3/3.5 kV

Temperature range: during installation: up to -15 °C; during operation: from -50 to +50 °C; in emergency mode: no more than +130 °C/8 hours per day.

Bending radius (minimum): single-core cables: at least 10 diameters; multi-core cables: at least 7.5 diameters.

NHXMH (ППГнг-HF)

Number and nominal cross-section of cores

(mm²) P

 

 

 

 

 

 

 

Rated cable diameter (mm)

Estimated weight of 1 km of cable

(kg) (reference)

Electrical resistance of conductors,

not more than (Ohm/km)

 

1 x 1,5

5,4

42

12,1

1 x 2,5

5,8

54

7,41

1 x 4

6,6

76

4,61

1 x 6

7,1

98

3,08

1 x 10

7,9

139

1,83

1 x 16

9,3

201

1,15

1 x 25

10,8

296

0,727

1 x 35

11,9

391

0,524

1 x 50

13,8

534

0,387

1 x 70

15,3

731

0,268

1 x 95

17,4

985

0,193

1 x 120

19

1 188

0,153

1 x 150

20,5

1 462

0,124

1 x 185

22,9

1 853

0,0991

1 x 240

25,6

2 320

0,0754

2 x 1,5

11

120

12,1

2 x 2,5

12

152

7,41

2 x 4

14

216

4,61

2 x 6

15

272

3,08

2 x 10

16

385

1,83

2 x 16

19

552

1,15

2 x 25

23

831

0,727

2 x 35

25

1 100

0,524

2 x 50

29

1 472

0,387

2 x 70

32

1 970

0,268

2 x 95

36

2 640

0,193

2 x 120

39

3 149

0,153

2 x 150

42

3 853

0,124

2 x 185

47

4 879

0,0991

2 x 240

53

6 159

0,0754

3 x 1,5

12

137

12,1

3 x 2,5

13

179

7,41

3 x 4

15

257

4,61

3 x 6

16

338

3,08

3 x 10

17

478

1,83

3 x 16

20

695

1,15

3 x 25

24

1 055

0,727

3 x 35

27

1 406

0,524

3 x 50

30

1 896

0,387

3 x 70

34

2 257

0,268

3 x 95

38

3 451

0,193

3 x 120

42

4 142

0,153

3 x 150

45

5 098

0,124

3 x 185

50

6 463

0,0991

3 x 240

57

8 145

0,0754

4 x 1,5

13

161

12,1

4 x 2,5

13

213

7,41

4 x 4

16

316

4,61

4 x 6

17

411

3,08

4 x 10

19

589

1,83

4 x 16

22

874

1,15

4 x 25

26

1 331

0,727

4 x 35

29

1 764

0,524

4 x 50

33

2 416

0,387

4 x 70

37

3 266

0,268

4 x 95

42

4 414

0,193

4 x 120

46

5 276

0,153

4 x 150

50

6 530

0,124

4 x 185

56

8 278

0,0991

4 x 240

63

10 483

0,0754

5 x 1,5

13

187

12,1

5 x 2,5

14

250

7,41

5 x 4

17

373

4,61

5 x 6

19

488

3,08

5 x 10

21

705

1,83

5 x 16

24

1 051

1,15

5 x 25

29

1 605

0,727

5 x 35

32

2 148

0,524

5 x 50

37

2 927

0,387

5 x 70

42

3 966

0,268

5 x 95

47

5 391

0,193

5 x 120

51

6 470

0,153

КСВВнг-LS

Single-core signal cable, flame retardant and with low smoke and gas emission

Structure Application Characteristics

Cable with single-wire copper conductors with a diameter of 0.40 mm, with insulation and sheath made of PVC plastic compound, which does not support or spread combustion. Used for internal laying.

KSVVng-LS cable is used to connect the QMS to the security alarm system, and is also often used to connect low-current equipment. The cable uses copper as the core material. This cable has conductive cores with a cross section of 0.40 mm.

TECHNICAL SPECIFICATIONS:

Cross-section-0.4 mm2

Number of cores: from 2mm to 20mm

Presence of screen-No

Conductor material-Copper

Feature-The material does not support combustion and the spread of fire

Name:

2*0,4 мм КСВВнг-LS

4*0,4 мм КСВВнг-LS

6*0,4 мм КСВВнг-LS

8*0,4 мм КСВВнг-LS

10*0,4 мм КСВВнг-LS

12*0,4 мм КСВВнг-LS

14*0,4 мм КСВВнг-LS

16*0,4 мм КСВВнг-LS

18*0,4 мм КСВВнг-LS

20*0,4 мм КСВВнг-LS

H05 Z-U / H07 Z-U

Single-core installation wire, in a halogen-free sheath with low smoke emission.

Structure Application Characteristics

The cable consists of: a conductive core - class 5 multi-wire copper, with core insulation made of a special low-smoke, halogen-free compound that does not support combustion.

The wire is used for stationary laying, installation inside electrical equipment, as well as for lighting. It is allowed to lay in cable ducts under plaster, as well as alarm and control systems. Suitable for use in hotels, hospitals, metro, airports, etc. to ensure the safety of people and technical building equipment in the event of a fire.

Rated voltage: 300/500 V

Test voltage: 2 kV/50 Hz

Temperature range: laying temperature min. +5°C, during operation: from -5°C to +70°C conductor temperature: max. +90 °C short-circuit: max. +250 °C/5 s

Bending radius (minimum): 4 cable diameters min.

Core marking: black (bk), blue (bu), brown (bn), green-yellow, (gnye), gray (gy)

 

FEATURES:

H07 Z-U

Nominal voltage: 450/750 V

Test voltage: 2.5 kV/50 Hz

Temperature range: laying temperature min. +5°C, during operation: from -5°C to +90°C conductor temperature: max. +90 °C short-circuit: max. +250 °C/5 s

Bending radius (minimum): 4 cable diameters min.

Core marking: black (bk), blue (bu), brown (bn), green-yellow, (gnye), grey (gy)

Nominal cross-section (mm²)

Electrical resistance of conductors, no more than (Ohm/km)

Estimated wire diameter (mm)

Estimated total mass of 1 km of wire (kg) (reference)

H05 Z-U

0,5

36,000

2

10

0,75

24,500

2,2

15

1

18,100

2,4

15

H05Z-K

0,5

39,000

2,2

10

0,75

26,000

2,4

15

1

19,500

2,6

15

H07 Z-U

1,5

12,100

3

20

2,5

7,410

3,5

30

4

4,610

4

45

H07Z-R

6

3,08

5

65

10

1,83

6,5

110

16

1,15

7,5

175

25

0,727

9

275

35

0,524

10

365

50

0,387

12

490

70

0,268

14

700

95

0,193

16,5

920

120

0,153

18,5

1 150

H07Z-K

1,5

13,3

2,9

20

2,5

7,98

3,6

31

4

4,95

4,4

50

6

3,3

4,7

69

10

1,91

6

110

16

1,21

7,5

170

25

0,78

9,5

255

35

0,554

11

345

50

0,386

13

490

70

0,272

15

700

95

0,206

17

930

120

0,161

18,5

1 150