Cable with copper conductors, silicone rubber insulation, filler, sheath made of halogen-free polymer compositions
The cable consists of: Conductive copper core 1, 2 classes according to GOST 22483, IEC 60228. FLEX – 3-5 classes according to GOST 22483, IEC 60228, silicone rubber insulation, halogen-free filling mm2 inclusive, it is allowed to apply an outer sheath with filling the cavities between the cores with the material of the outer sheath. In this case, the inner filling is not applied, the sheath is made of a polymer composition that does not contain halogens.
Flame-resistant halogen-free cables are intended for power transmission systems in stationary installations, as well as for connection to stationary electrical appliances, devices, and assembly of electrical switchgear for power networks with a rated voltage of up to 0.6/1 kV. The cables provide transmission of electrical energy, control and management signals to electrical equipment, the functioning of which in fire conditions is mandatory for rescue operations. They are used at facilities with increased fire safety requirements for single and bundled cables in rooms, tunnels, trays, pipes, flexible hoses in the absence of danger of mechanical damage and protection from ultraviolet rays.
Rated voltage: 0.6/1 kV
Test voltage: 4 kV/50 Hz
Temperature range: during installation: up to -15 °C during operation: from -30 °C to +50 °C cores: no more than +90 °C short circuit: no more than +250 °C/4 sec in emergency mode: no more than +130 °C/8 h per day
Bending radius (minimum): single-core cables: no less than 10 diameters; multi-core cables: no less than 7.5 diameters for cables with FLEX index: no less than 6 diameters
Number and nominal cross-section of conductors (mm²) | Rated cable diameter (mm) | Estimated weight of 1 km of cable (kg) (reference) | Electrical resistance of wires, in accordance with GOST 22483, IEC 60228, not more than (Ohm/km) |
HXH-FE 180E30, (N)HXH-FE 180E30 | |||
1 x 25 | 10,4 | 307,5 | 0,727 |
1 x 35 | 11,7 | 405,1 | 0,524 |
1 x 50 | 13,5 | 554,7 | 0,387 |
1 x 70 | 15,1 | 755,1 | 0,268 |
1 x 95 | 17,1 | 1 024,90 | 0,193 |
1 x 120 | 19,1 | 1 233,90 | 0,153 |
1 x 150 | 20,4 | 1 524,20 | 0,124 |
1 x 185 | 23 | 1 938,60 | 0,0991 |
1 x 240 | 25,8 | 2 426,10 | 0,0754 |
2 x 1,5 | 8,5 | 112,8 | 12,1 |
2 x 2,5 | 9,3 | 145,1 | 7,41 |
2 x 4 | 10,3 | 191,4 | 4,61 |
2 x 6 | 11,3 | 247,4 | 3,08 |
2 x 10 | 13 | 358,1 | 1,83 |
2 x 16 | 16,8 | 602,4 | 1,15 |
3 x 1,5 | 9 | 132,8 | 12,1 |
3 x 2,5 | 9,9 | 174,5 | 7,41 |
3 x 4 | 10,9 | 234,8 | 4,61 |
3 x 6 | 12,2 | 314,9 | 3,08 |
3 x 10 | 13,9 | 454,2 | 1,83 |
3 x 16 | 17,8 | 753,3 | 1,15 |
4 x 1,5 | 9,8 | 158,3 | 12,1 |
4 x 2,5 | 10,7 | 210,5 | 7,41 |
4 x 4 | 12,1 | 292,6 | 4,61 |
4 x 6 | 13,3 | 386,8 | 3,08 |
4 x 10 | 15,2 | 563,8 | 1,83 |
4 x 16 | 19,6 | 942 | 1,15 |
4 x 25 | 23,8 | 1 432,70 | 0,727 |
4 x 35 | 26,8 | 1 888,30 | 0,524 |
4 x 50 | 30,8 | 2 569,80 | 0,387 |
4 x 70 | 35,2 | 3 492,80 | 0,268 |
4 x 95 | 40,4 | 4 745,60 | 0,193 |
4 x 120 | 45,6 | 5 744,80 | 0,153 |
4 x 150 | 48,5 | 7 053,60 | 0,124 |
4 x 185 | 54,4 | 8 938,80 | 0,0991 |
4 x 240 | 61,7 | 11 301,90 | 0,0754 |
5 x 1,5 | 10,7 | 186,3 | 12,1 |
5 x 2,5 | 11,7 | 249,7 | 7,41 |
5 x 4 | 13,2 | 349,5 | 4,61 |
5 x 6 | 14,6 | 463,9 | 3,08 |
5 x 10 | 16,7 | 680,5 | 1,83 |
5 x 16 | 21,5 | 1 130,00 | 1,15 |
5 x 25 | 26,1 | 1 724,50 | 1,727 |
5 x 35 | 29,7 | 2 293,20 | 0,524 |
5 x 50 | 33,9 | 3 107,20 | 0,387 |
5 x 70 | 38,8 | 4 228,30 | 0,268 |
5 x 95 | 44,7 | 5 754,90 | 0,193 |
5 x 120 | 50,7 | 6 985,60 | 0,153 |
Cable with copper conductors, silicone rubber insulation, filler, sheath made of halogen-free polymer compositions
The cable consists of: Conductive copper core 1, 2 classes according to GOST 22483, IEC 60228. FLEX – 3-5 classes according to GOST 22483, IEC 60228, silicone rubber insulation, halogen-free filling mm2 inclusive, it is allowed to apply an outer sheath with filling the cavities between the cores with the material of the outer sheath. In this case, the inner filling is not applied, the sheath is made of a polymer composition that does not contain halogens.
Flame-resistant halogen-free cables are intended for power transmission systems in stationary installations, as well as for connection to stationary electrical appliances, devices, and assembly of electrical switchgear for power networks with a rated voltage of up to 0.6/1 kV. The cables provide transmission of electrical energy, control and management signals to electrical equipment, the functioning of which in fire conditions is mandatory for rescue operations. They are used at facilities with increased fire safety requirements for single and bundled cables in rooms, tunnels, trays, pipes, flexible hoses in the absence of danger of mechanical damage and protection from ultraviolet rays.
Rated voltage: 0.6/1 kV
Test voltage: 4 kV/50 Hz
Temperature range: during installation: up to -15 °C during operation: from -30 °C to +50 °C cores: no more than +90 °C short circuit: no more than +250 °C/4 sec in emergency mode: no more than +130 °C/8 h per day
Bending radius (minimum): single-core cables: no less than 10 diameters; multi-core cables: no less than 7.5 diameters for cables with FLEX index: no less than 6 diameters
Number and nominal cross-section of cores (mm²) | Rated cable diameter (mm) | Estimated weight of 1 km of cable (kg) (reference) | Electrical resistance of wires, in accordance with GOST 22483, IEC 60228, not more than (Ohm/km) |
HXH-FE 180/E90, (N)HXH-FE 180/E90 | |||
2 x 1,5 | 12,9 | 235 | 12,1 |
2 x 2,5 | 13,7 | 273 | 7,41 |
2 x 4 | 14,7 | 355 | 4,61 |
2 x 6 | 15,7 | 426 | 3,08 |
2 x 10 | 17,2 | 551 | 1,83 |
2 x 16 | 19,6 | 750 | 1,15 |
2 x 25 | 22,9 | 1 070 | 0,727 |
2 x 35 | 25,4 | 1 364 | 0,524 |
2 x 50 | 28,8 | 1 804 | 0,387 |
2 x 70 | 32,6 | 2 395 | 0,268 |
2 x 95 | 37,2 | 3 201 | 0,193 |
2 x 120 | 40,4 | 3 802 | 0,153 |
2 x 150 | 44,2 | 4 666 | 0,124 |
2 x 185 | 49,4 | 5 871 | 0,0991 |
2 x 240 | 55,8 | 7 417 | 0,0754 |
3 x 1,5 | 13,5 | 287 | 12,1 |
3 x 2,5 | 14,4 | 342 | 7,41 |
3 x 4 | 15,4 | 417 | 4,61 |
3 x 6 | 16,4 | 508 | 3,08 |
3 x 10 | 18,1 | 674 | 1,83 |
3 x 16 | 20,7 | 935 | 1,15 |
3 x 25 | 24,3 | 1 354 | 0,721 |
3 x 35 | 27,2 | 1 761 | 0,254 |
3 x 50 | 30,8 | 2 343 | 0,387 |
3 x 70 | 34,9 | 3 129 | 0,268 |
3 x 95 | 39,8 | 4 202 | 0,193 |
3 x 120 | 43,7 | 5 051 | 0,153 |
3 x 150 | 47,3 | 6 151 | 0,124 |
3 x 185 | 52,9 | 7 757 | 0,0991 |
3 x 240 | 59,7 | 9 801 | 0,0754 |
4 x 1,5 | 14,4 | 326 | 12,1 |
4 x 2,5 | 15,3 | 393 | 7,41 |
4 x 4 | 16,5 | 486 | 4,61 |
4 x 6 | 17,7 | 599 | 3,08 |
4 x 10 | 19,6 | 807 | 1,83 |
4 x 16 | 22,4 | 1 130 | 1,15 |
4 x 25 | 26,4 | 1 652 | 0,727 |
4 x 35 | 29,6 | 2 158 | 0,524 |
4 x 50 | 34,3 | 2 943 | 0,387 |
4 x 70 | 38,3 | 3 889 | 0,268 |
4 x 95 | 44,2 | 5 286 | 0,193 |
4 x 120 | 47,6 | 6 236 | 0,153 |
4 x 150 | 52,3 | 7 727 | 0,124 |
4 x 185 | 58,8 | 9 813 | 0,0991 |
4 x 240 | 66 | 12 284 | 0,0754 |
5 x 1,5 | 15,4 | 367 | 12,1 |
5 x 2,5 | 16,5 | 447 | 7,41 |
5 x 4 | 17,8 | 558 | 4,61 |
5 x 6 | 19,1 | 693 | 3,08 |
5 x 10 | 21,2 | 943 | 1,83 |
5 x 16 | 24,4 | 1 330 | 1,15 |
5 x 25 | 29,1 | 1 971 | 1,727 |
5 x 35 | 33,3 | 2 638 | 0,524 |
5 x 50 | 37,8 | 3 520 | 0,387 |
5 x 70 | 42,9 | 4 736 | 0,268 |
5 x 95 | 49 | 6 370 | 0,193 |
5 x 120 | 53,2 | 7 582 | 0,153 |
The cable is fire-resistant with copper conductors twisted in pairs, silicone rubber insulation, aluminum screen, and a halogen-free polymer sheath.
The cable consists of: a conductive core - copper, single-wire, class A according to GOST 4809:2007; silicone rubber insulation; insulated cores twisted into pairs, pairs - into bundles, over the bundle is wrapped with PET film, an aluminum foil screen, a sheath made of non-flammable, halogen-free polymer composition.
Transmission of electrical signals of information, control and management in industrial electronics, fire and security alarm systems with a rated voltage of up to 300 V. For laying in facilities with increased fire safety requirements, where cable operation in fire conditions is mandatory, for single and bundle laying in rooms, tunnels, in trays, boxes, flexible sleeves in the absence of danger of mechanical damage.
Rated voltage: 0.3 kV
Test voltage: 2 kV
Temperature range: during installation: not lower than -5 ° C during operation: from -30 ° C to +70 ° C heating of cores: not higher than +70 ° C
Bending radius (minimum): not less than 7.5 diameters
Number and nominal cross-section of cores (pcs x mm) | Estimated wire diameter (mm) | Estimated mass of 1 km of cable (kg) |
1 х 2 х 0,8 |
|
|
2 х 2 х 0,8 | 7,5 | 65 |
4 х 2 х 08 | 9,5 | 104 |
6 х 2 х 08 | ||
8 х 2 х 0,8 | 11,5 | 165 |
10х 2 х 0,8 | ||
12 х 2 х 0,8 | 13,5 | 235 |
16 х 2 х 0,8 | 15 | 300 |
20 х 2 х 0,8 | 16,5 | 361 |
The cable is fire-resistant with copper conductors twisted in pairs, silicone rubber insulation, aluminum screen, and a halogen-free polymer sheath.
The cable consists of: a conductive core - copper, single-wire, class A according to GOST 4809:2007; silicone rubber insulation; insulated cores twisted into pairs, pairs - into bundles, over the bundle is wrapped with PET film, an aluminum foil screen, a sheath made of non-spreading, halogen-free polymer composition.
Transmission of electrical signals of information, control and management in industrial electronics, fire and security alarm systems with a rated voltage of up to 300 V. For laying in facilities with increased fire safety requirements, where cable operation in fire conditions is mandatory, for single and bundle laying in rooms, tunnels, in trays, boxes, flexible sleeves in the absence of danger of mechanical damage.
Rated voltage: 0.3 kV
Test voltage: 2 kV
Temperature range: during installation: not lower than -5 ° C during operation: from -30 ° C to +70 ° C heating of cores: not higher than +70 ° C
Bending radius (minimum): not less than 7.5 diameters
Number and nominal cross-section of cores (pcs x mm) | Estimated wire diameter (mm) | Estimated mass of 1 km of cable (kg) |
1 х 2 х 0,8 |
|
|
2 х 2 х 0,8 | 8,5 | 83 |
4 х 2 х 0,8 | 11,5 | 138 |
6 х 2 х 0,8 | ||
8 х 2 х 0,8 | 15 | 243 |
10 х 2 х 0,8 | ||
12 х 2 х 0,8 | 18,5 | 351 |
16 х 2 х 0,8 | 20,5 | 441 |
20 х 2 х 0,8 | 24 | 557 |
- Bare copper conductor, solid
- Core insulation: HFFR compound
- Core color coding according to
- 4 cores twisted in a quadruple star,
- Tape shielded with tinned copper drain wire (0.80 mm)
- Outer sheath made of HFFR compound
Sheath color red.
Halogen-free cables J-H(St)H...Bd are used for signaling, transmission and telecommunications in fixed indoor wiring. The screen provides protection against external interference. Non-flammable cables are used in schools, airports, hospitals, etc., where in the event of a fire, the release of toxic gases into the environment is unacceptable. In the event of a fire, these cables delay the spread of fire and emit a minimum amount of smoke.
Number of cores: from 1 to 10 pairs
Diameter: from 0.6 to 1.38 mm
Permissible temperature limits:
- stationary - from -30 ° C to +70 ° C
- mobile - from -5 ° C to +50 ° C
Insulation resistance (loop): 0.60 mm = 130 Ohm/km
Insulation resistance, min.: 100 MOm/km
Total capacitance (800 Hz), max.: 100 nF/m
Capacitive unbalance (k), min.: 300 pF/100m
Operating voltage, peak: 300 V
Test voltage (AC 50 Hz): core/core - 800 V
Minimum cable bending radius: 7.5 x cable Ø
Name | Number of cores / Ø, mm | External Ø, mm | Copper weight kg/km | Cable weight kg/km |
J-H(St)H Bd 1x2x0,60 мм | 1x2xØ0,60 | 4,6 | 8,15 | 31 |
J-H(St)H Bd 2x2x0,60 мм | 2x2xØ0,60 | 5,1 | 13,67 | 42 |
J-H(St)H Bd 4x2x0,60 мм | 4x2xØ0,60 | 8 | 24,71 | 75 |
J-H(St)H Bd 6x2x0,60 мм | 6x2xØ0,60 | 8,5 | 35,75 | 94 |
J-H(St)H Bd 10x2x0,60 мм | 10x2xØ0,60 | 10,1 | 57,83 | 136 |
J-H(St)H Bd 1x2x0,80 мм | 1x2xØ0,80 | 5,4 | 14,61 | 44 |
J-H(St)H Bd 2x2x0,80 мм | 2x2xØ0,80 | 6,1 | 24,61 | 63 |
J-H(St)H Bd 4x2x0,80 мм | 4x2xØ0,80 | 10 | 44,61 | 114 |
J-H(St)H Bd 6x2x0,80 мм | 6x2xØ0,80 | 10,6 | 64,55 | 147 |
J-H(St)H Bd 10x2x0,80 мм | 10x2xØ0,80 | 12,5 | 104,39 | 228 |
J-H(St)H Bd 20x2x0,80 мм | 20x2xØ0,80 | 16,6 | 203,99 | 404 |
Cable with cross-linked polyethylene insulation and a sheath made of halogen-free, flame-retardant polymer compositions with low smoke and gas emission.
The cable consists of:
Cables are intended for transmission and distribution of electric energy in stationary alternating current installations with a voltage of 0.6/1 kV. Cables are used for laying in production and office premises in which computers and other microprocessor equipment are installed, as well as in subway structures, residential and public buildings, cable structures and premises with increased fire safety requirements. The cable meets fire safety requirements
Cables are intended for transmission and distribution of electric energy in stationary alternating current installations with a voltage of 0.6/1 kV. Cables are used for laying in production and office premises in which computers and other microprocessor equipment are installed, as well as in subway structures, residential and public buildings, cable structures and premises with increased fire safety requirements. The cable meets fire safety requirements
N2XH (ПГнг-HF) | |||
Number and nominal cross-section of conductors (mm²)
| Rated cable diameter (mm) | Estimated weight of 1 km of cable (kg) (reference) | Electrical resistance of conductors, not more than (Ohm/km) |
1 x 1,5 | 5,4 | 42 | 12,1 |
1 x 2,5 | 5,8 | 54 | 7,41 |
1 x 4 | 6,6 | 76 | 4,61 |
1 x 6 | 7,1 | 98 | 3,08 |
1 x 10 | 7,9 | 139 | 1,83 |
1 x 16 | 9,3 | 201 | 1,15 |
1 x 25 | 10,8 | 296 | 0,727 |
1 x 35 | 11,9 | 391 | 0,524 |
1 x 50 | 13,8 | 534 | 0,387 |
1 x 70 | 15,3 | 731 | 0,268 |
1 x 95 | 17,4 | 985 | 0,193 |
1 x 120 | 19 | 1 188 | 0,153 |
1 x 150 | 20,5 | 1 462 | 0,124 |
1 x 185 | 22,9 | 1 853 | 0,0991 |
1 x 240 | 25,6 | 2 320 | 0,0754 |
2 x 1,5 | 9,3 | 120 | 12,1 |
2 x 2,5 | 10,1 | 152 | 7,41 |
2 x 4 | 11,9 | 216 | 4,61 |
2 x 6 | 12,9 | 272 | 3,08 |
2 x 10 | 14,6 | 385 | 1,83 |
2 x 16 | 17 | 552 | 1,15 |
2 x 25 | 20,5 | 831 | 0,727 |
2 x 35 | 23,2 | 1 100 | 0,524 |
2 x 50 | 26,4 | 1 472 | 0,387 |
2 x 70 | 29,8 | 1 970 | 0,268 |
2 x 95 | 33,8 | 2 640 | 0,193 |
2 x 120 | 36,8 | 3 149 | 0,153 |
2 x 150 | 39,8 | 3 853 | 0,124 |
2 x 185 | 44,6 | 4 879 | 0,0991 |
2 x 240 | 50,4 | 6 159 | 0,0754 |
3 x 1,5 | 9,8 | 137 | 12,1 |
3 x 2,5 | 10,6 | 179 | 7,41 |
3 x 4 | 12,5 | 257 | 4,61 |
3 x 6 | 13,8 | 338 | 3,08 |
3 x 10 | 15,5 | 478 | 1,83 |
3 x 16 | 18 | 695 | 1,15 |
3 x 25 | 21,8 | 1 055 | 0,727 |
3 x 35 | 24,6 | 1 406 | 0,524 |
3 x 50 | 28,1 | 1 896 | 0,387 |
3 x 70 | 31,7 | 2 257 | 0,268 |
3 x 95 | 36 | 3 451 | 0,193 |
3 x 120 | 39,4 | 4 142 | 0,153 |
3 x 150 | 42,6 | 5 098 | 0,124 |
3 x 185 | 47,8 | 6 463 | 0,0991 |
3 x 240 | 54 | 8 145 | 0,0754 |
4 x 1,5 | 10,5 | 161 | 12,1 |
4 x 2,5 | 11,5 | 213 | 7,41 |
4 x 4 | 13,8 | 316 | 4,61 |
4 x 6 | 15 | 411 | 3,08 |
4 x 10 | 16,9 | 589 | 1,83 |
4 x 16 | 20 | 874 | 1,15 |
4 x 25 | 24,1 | 1 331 | 0,727 |
4 x 35 | 27,1 | 1 764 | 0,524 |
4 x 50 | 31,4 | 2 416 | 0,387 |
4 x 70 | 35,5 | 3 266 | 0,268 |
4 x 95 | 40,2 | 4 414 | 0,193 |
4 x 120 | 43,8 | 5 276 | 0,153 |
4 x 150 | 47,6 | 6 530 | 0,124 |
4 x 185 | 53,3 | 8 278 | 0,0991 |
4 x 240 | 60,7 | 10 483 | 0,0754 |
5 x 1,5 | 11,4 | 187 | 12,1 |
5 x 2,5 | 12,5 | 250 | 7,41 |
5 x 4 | 15 | 373 | 4,61 |
5 x 6 | 16,4 | 488 | 3,08 |
5 x 10 | 18,5 | 705 | 1,83 |
5 x 16 | 21,9 | 1 051 | 1,15 |
5 x 25 | 26,6 | 1 605 | 0,727 |
5 x 35 | 30,1 | 2 148 | 0,524 |
5 x 50 | 34,6 | 2 927 | 0,387 |
5 x 70 | 39,2 | 3 966 | 0,268 |
5 x 95 | 44,7 | 5 391 | 0,193 |
5 x 120 | 48,9 | 6 470 | 0,153 |
Cable with aluminum conductors, with cross-linked polyethylene insulation and a sheath made of halogen-free, flame-retardant polymer compositions with low smoke and gas emission.
The cable consists of:
Cables are intended for transmission and distribution of electric energy in stationary alternating current installations with a voltage of 0.6/1 kV. Cables are used for laying in production and office premises in which computers and other microprocessor equipment are installed, as well as in subway structures, residential and public buildings, cable structures and premises with increased fire safety requirements. The cable meets fire safety requirements
The cables are designed for transmission and distribution of electrical energy in stationary alternating current installations with a voltage of 0.66/1 kV. The cables are used for laying in production and office premises in which computers and other microprocessor equipment are installed, as well as in subway structures, residential and public buildings, cable structures and premises with increased fire safety requirements.
Rated voltage: 0.6/1 kV
Test voltage: 3/3.5 kV
Temperature range:
during installation: up to -15 °C;
during operation: from -50 to +50 °C in emergency mode: no more than +130 °C/8 hours per day
Bending radius (minimum): single-core cables: not less than 10 diameters; multi-core cables: not less than 7.5 diameters
NА2XH (АПвПГнг-HF) | |||
Number and nominal cross-section of cores (mm²) | Rated cable diameter (mm) | Estimated weight of 1 km of cable (kg) (reference) | Electrical resistance of conductors, not more than (Ohm/km) |
1 х 16 | 9,3 | 109 | 1,91 |
1 х 25 | 10,8 | 153 | 1,2 |
1 х 35 | 11,9 | 187 | 0,868 |
1 х 50 | 13,8 | 243 | 0,641 |
1 х 70 | 15,3 | 318 | 0,443 |
1 х 95 | 17,4 | 409 | 0,32 |
1 х 120 | 19 | 505 | 0,253 |
1 х 150 | 20,5 | 615 | 0,206 |
1 х 185 | 22,9 | 757 | 0,164 |
1 х 240 | 25,6 | 953 | 0,125 |
2 х 2,5 | 10,12 | 138 | 12,1 |
2 х 4 | 11,86 | 167 | 7,41 |
2 х 6 | 12,86 | 201 | 5,11 |
2 х 10 | 14,62 | 262 | 3,08 |
2 х 16 | 16,44 | 364 | 1,91 |
2 х 25 | 20,5 | 547 | 1,2 |
2 х 35 | 23,2 | 666 | 0,868 |
2 х 50 | 26,4 | 919 | 0,641 |
2 х 70 | 29,8 | 1 199 | 0,443 |
2 х 95 | 33,8 | 1 583 | 0,32 |
2 х 120 | 36,8 | 1 946 | 0,253 |
2 х 150 | 39,8 | 2 387 | 0,206 |
2 х 185 | 44,6 | 3 003 | 0,164 |
2 х 240 | 50,4 | 3 678 | 0,125 |
3 х 2,5 | 10,62 | 149 | 12,1 |
3 х 4 | 12,49 | 181 | 7,41 |
3 х 6 | 13,77 | 220 | 5,11 |
3 х 10 | 15,45 | 290 | 3,08 |
3 х 16 | 18,01 | 406 | 1,91 |
3 х 25 | 21,75 | 611 | 1,2 |
3 х 35 | 24,64 | 751 | 0,868 |
3 х 50 | 28,08 | 1 031 | 0,641 |
3 х 70 | 31,72 | 1 371 | 0,443 |
3 х 95 | 36,01 | 1 822 | 0,32 |
3 х 120 | 39,43 | 2 190 | 0,253 |
3 х 150 | 42,64 | 2 696 | 0,206 |
3 х 185 | 47,77 | 3 392 | 0,164 |
3 х 240 | 53,99 | 4 193 | 0,125 |
4 х 2,5 | 11,5 | 168 | 12,1 |
4 х 4 | 13,79 | 207 | 7,41 |
4 х 6 | 15 | 253 | 5,11 |
4 х 10 | 16,88 | 337 | 3,08 |
4 х 16 | 19,27 | 494 | 1,91 |
4 х 25 | 24,12 | 717 | 1,2 |
4 х 35 | 27,14 | 912 | 0,868 |
4 х 50 | 31,39 | 1 234 | 0,641 |
4 х 70 | 35,45 | 1 659 | 0,443 |
4 х 95 | 40,23 | 2 159 | 0,32 |
4 х 120 | 43,84 | 2 621 | 0,253 |
4 х 150 | 47,62 | 3 252 | 0,206 |
4 х 185 | 53,32 | 4 064 | 0,164 |
4 х 240 | 60,67 | 5 054 | 0,125 |
5 х 2,5 | 12,47 | 190 | 12,1 |
5 х 4 | 15,02 | 235 | 7,41 |
5 х 6 | 16,37 | 290 | 5,11 |
5 х 10 | 18,48 | 388 | 3,08 |
5 х 16 | 21,13 | 571 | 1,91 |
5 х 25 | 26,55 | 859 | 1,2 |
5 х 35 | 30,12 | 1 063 | 0,868 |
5 х 50 | 34,64 | 1 439 | 0,641 |
5 х 70 | 39,16 | 1 940 | 0,443 |
5 х 95 | 44,69 | 2 553 | 0,32 |
5 х 120 | 48,94 | 3 118 | 0,253 |
Cable with aluminum conductors, with cross-linked polyethylene insulation and a sheath made of halogen-free, flame-retardant polymer compositions with low smoke and gas emission.
The cable consists of: a conductive core 1, 2, insulation made of a halogen-free polymer composition, filling of a halogen-free, non-flammable composition, sheath made of a halogen-free polymer composition.
Cables are designed for transmission and distribution of electrical energy in stationary alternating current installations with a voltage of 0.6/1 kV. Cables are used for laying in production and office premises in which computers and other microprocessor equipment are installed, as well as in subway structures, residential and public buildings, cable structures and premises with increased fire safety requirements.
Rated voltage: 0.6/1 kV
Test voltage: 3/3.5 kV
Temperature range: during installation: up to -15 °C; during operation: from -50 to +50 °C; in emergency mode: no more than +130 °C/8 hours per day.
Bending radius (minimum): single-core cables: at least 10 diameters; multi-core cables: at least 7.5 diameters.
NHXMH (ППГнг-HF) | |||
Number and nominal cross-section of cores (mm²) P
| Rated cable diameter (mm) | Estimated weight of 1 km of cable (kg) (reference) | Electrical resistance of conductors, not more than (Ohm/km)
|
1 x 1,5 | 5,4 | 42 | 12,1 |
1 x 2,5 | 5,8 | 54 | 7,41 |
1 x 4 | 6,6 | 76 | 4,61 |
1 x 6 | 7,1 | 98 | 3,08 |
1 x 10 | 7,9 | 139 | 1,83 |
1 x 16 | 9,3 | 201 | 1,15 |
1 x 25 | 10,8 | 296 | 0,727 |
1 x 35 | 11,9 | 391 | 0,524 |
1 x 50 | 13,8 | 534 | 0,387 |
1 x 70 | 15,3 | 731 | 0,268 |
1 x 95 | 17,4 | 985 | 0,193 |
1 x 120 | 19 | 1 188 | 0,153 |
1 x 150 | 20,5 | 1 462 | 0,124 |
1 x 185 | 22,9 | 1 853 | 0,0991 |
1 x 240 | 25,6 | 2 320 | 0,0754 |
2 x 1,5 | 11 | 120 | 12,1 |
2 x 2,5 | 12 | 152 | 7,41 |
2 x 4 | 14 | 216 | 4,61 |
2 x 6 | 15 | 272 | 3,08 |
2 x 10 | 16 | 385 | 1,83 |
2 x 16 | 19 | 552 | 1,15 |
2 x 25 | 23 | 831 | 0,727 |
2 x 35 | 25 | 1 100 | 0,524 |
2 x 50 | 29 | 1 472 | 0,387 |
2 x 70 | 32 | 1 970 | 0,268 |
2 x 95 | 36 | 2 640 | 0,193 |
2 x 120 | 39 | 3 149 | 0,153 |
2 x 150 | 42 | 3 853 | 0,124 |
2 x 185 | 47 | 4 879 | 0,0991 |
2 x 240 | 53 | 6 159 | 0,0754 |
3 x 1,5 | 12 | 137 | 12,1 |
3 x 2,5 | 13 | 179 | 7,41 |
3 x 4 | 15 | 257 | 4,61 |
3 x 6 | 16 | 338 | 3,08 |
3 x 10 | 17 | 478 | 1,83 |
3 x 16 | 20 | 695 | 1,15 |
3 x 25 | 24 | 1 055 | 0,727 |
3 x 35 | 27 | 1 406 | 0,524 |
3 x 50 | 30 | 1 896 | 0,387 |
3 x 70 | 34 | 2 257 | 0,268 |
3 x 95 | 38 | 3 451 | 0,193 |
3 x 120 | 42 | 4 142 | 0,153 |
3 x 150 | 45 | 5 098 | 0,124 |
3 x 185 | 50 | 6 463 | 0,0991 |
3 x 240 | 57 | 8 145 | 0,0754 |
4 x 1,5 | 13 | 161 | 12,1 |
4 x 2,5 | 13 | 213 | 7,41 |
4 x 4 | 16 | 316 | 4,61 |
4 x 6 | 17 | 411 | 3,08 |
4 x 10 | 19 | 589 | 1,83 |
4 x 16 | 22 | 874 | 1,15 |
4 x 25 | 26 | 1 331 | 0,727 |
4 x 35 | 29 | 1 764 | 0,524 |
4 x 50 | 33 | 2 416 | 0,387 |
4 x 70 | 37 | 3 266 | 0,268 |
4 x 95 | 42 | 4 414 | 0,193 |
4 x 120 | 46 | 5 276 | 0,153 |
4 x 150 | 50 | 6 530 | 0,124 |
4 x 185 | 56 | 8 278 | 0,0991 |
4 x 240 | 63 | 10 483 | 0,0754 |
5 x 1,5 | 13 | 187 | 12,1 |
5 x 2,5 | 14 | 250 | 7,41 |
5 x 4 | 17 | 373 | 4,61 |
5 x 6 | 19 | 488 | 3,08 |
5 x 10 | 21 | 705 | 1,83 |
5 x 16 | 24 | 1 051 | 1,15 |
5 x 25 | 29 | 1 605 | 0,727 |
5 x 35 | 32 | 2 148 | 0,524 |
5 x 50 | 37 | 2 927 | 0,387 |
5 x 70 | 42 | 3 966 | 0,268 |
5 x 95 | 47 | 5 391 | 0,193 |
5 x 120 | 51 | 6 470 | 0,153 |
Single-core signal cable, flame retardant and with low smoke and gas emission
Cable with single-wire copper conductors with a diameter of 0.40 mm, with insulation and sheath made of PVC plastic compound, which does not support or spread combustion. Used for internal laying.
KSVVng-LS cable is used to connect the QMS to the security alarm system, and is also often used to connect low-current equipment. The cable uses copper as the core material. This cable has conductive cores with a cross section of 0.40 mm.
TECHNICAL SPECIFICATIONS:
Cross-section-0.4 mm2
Number of cores: from 2mm to 20mm
Presence of screen-No
Conductor material-Copper
Feature-The material does not support combustion and the spread of fire
Name: |
2*0,4 мм КСВВнг-LS |
4*0,4 мм КСВВнг-LS |
6*0,4 мм КСВВнг-LS |
8*0,4 мм КСВВнг-LS |
10*0,4 мм КСВВнг-LS |
12*0,4 мм КСВВнг-LS |
14*0,4 мм КСВВнг-LS |
16*0,4 мм КСВВнг-LS |
18*0,4 мм КСВВнг-LS |
20*0,4 мм КСВВнг-LS |
Single-core installation wire, in a halogen-free sheath with low smoke emission.
The cable consists of: a conductive core - class 5 multi-wire copper, with core insulation made of a special low-smoke, halogen-free compound that does not support combustion.
The wire is used for stationary laying, installation inside electrical equipment, as well as for lighting. It is allowed to lay in cable ducts under plaster, as well as alarm and control systems. Suitable for use in hotels, hospitals, metro, airports, etc. to ensure the safety of people and technical building equipment in the event of a fire.
Rated voltage: 300/500 V
Test voltage: 2 kV/50 Hz
Temperature range: laying temperature min. +5°C, during operation: from -5°C to +70°C conductor temperature: max. +90 °C short-circuit: max. +250 °C/5 s
Bending radius (minimum): 4 cable diameters min.
Core marking: black (bk), blue (bu), brown (bn), green-yellow, (gnye), gray (gy)
FEATURES:
H07 Z-U
Nominal voltage: 450/750 V
Test voltage: 2.5 kV/50 Hz
Temperature range: laying temperature min. +5°C, during operation: from -5°C to +90°C conductor temperature: max. +90 °C short-circuit: max. +250 °C/5 s
Bending radius (minimum): 4 cable diameters min.
Core marking: black (bk), blue (bu), brown (bn), green-yellow, (gnye), grey (gy)
Nominal cross-section (mm²) | Electrical resistance of conductors, no more than (Ohm/km) | Estimated wire diameter (mm) | Estimated total mass of 1 km of wire (kg) (reference) |
H05 Z-U | |||
0,5 | 36,000 | 2 | 10 |
0,75 | 24,500 | 2,2 | 15 |
1 | 18,100 | 2,4 | 15 |
H05Z-K | |||
0,5 | 39,000 | 2,2 | 10 |
0,75 | 26,000 | 2,4 | 15 |
1 | 19,500 | 2,6 | 15 |
H07 Z-U | |||
1,5 | 12,100 | 3 | 20 |
2,5 | 7,410 | 3,5 | 30 |
4 | 4,610 | 4 | 45 |
H07Z-R | |||
6 | 3,08 | 5 | 65 |
10 | 1,83 | 6,5 | 110 |
16 | 1,15 | 7,5 | 175 |
25 | 0,727 | 9 | 275 |
35 | 0,524 | 10 | 365 |
50 | 0,387 | 12 | 490 |
70 | 0,268 | 14 | 700 |
95 | 0,193 | 16,5 | 920 |
120 | 0,153 | 18,5 | 1 150 |
H07Z-K | |||
1,5 | 13,3 | 2,9 | 20 |
2,5 | 7,98 | 3,6 | 31 |
4 | 4,95 | 4,4 | 50 |
6 | 3,3 | 4,7 | 69 |
10 | 1,91 | 6 | 110 |
16 | 1,21 | 7,5 | 170 |
25 | 0,78 | 9,5 | 255 |
35 | 0,554 | 11 | 345 |
50 | 0,386 | 13 | 490 |
70 | 0,272 | 15 | 700 |
95 | 0,206 | 17 | 930 |
120 | 0,161 | 18,5 | 1 150 |